Open-type cooling towers are heat dissipation devices powered by natural wind. Their open design eliminates the need for mechanical ventilation. Air circulation is achieved through louvers surrounding the water-spraying packing material, utilizing direct contact between water and air for heat exchange. They are suitable for environments with stable average annual wind speeds and dry climates. The maximum cooling capacity is 500 m³/h; exceeding this capacity requires mechanical or hybrid ventilation cooling towers. Industry standards require open-type cooling towers to be equipped with demisters, and the cooling water system should have continuous disinfection and chemical dosing devices, with cleaning at least once a year. The tower should not be located upwind of the direction of the most frequent wind during the air conditioning cooling season and must meet noise requirements.
The 2023 revised standard added corrosion protection clauses, requiring hot-dip galvanizing of the metal components of the louvers to achieve a coating thickness ≥85 μm. Additional protective measures are required under special climatic conditions, such as draining the water collection tank and covering it with a dust cover when the tower is not in use during winter.
Based on engineering measurements and optimization analysis, it is shown that replacing the nozzles with high-efficiency, energy-saving, and anti-clogging spiral nozzles, increasing the height of the cooling tower barrier structure, and updating and increasing the packing inside the tower can improve performance, while adding a frequency converter can achieve energy saving.