According to the *Hygienic Standard for Centralized Air Conditioning and Ventilation Systems in Public Places* (WS 10013-2023) and the *Hygienic Standard for Design of Public Places*:
Layout Requirements: The system must be at least 10 meters away from densely populated areas and fresh air intakes, and should not be located upwind of the fresh air intake in the direction of the most frequent wind direction during the air conditioning cooling season.
Structural Requirements: A demister should be installed to reduce water droplet dispersion. The cooling water system should be equipped with continuous disinfection and chemical dosing devices.
Layout Requirements: The system must be at least 10 meters away from densely populated areas and fresh air intakes, and should not be located upwind of the fresh air intake.
Structural Requirements: A demister must be installed to reduce water droplet dispersion. The disinfectant filling port diameter should be at least 50mm for easy chemical dosing.
Material Requirements: The inner wall of the water collection tank must be smooth and free of dead corners, and the drainage slope should be at least 2% to prevent microbial growth.
Noise requirements are also added, and the system should comply with the *Code for Sound Insulation Design of Civil Buildings*.
The revised standard in 2023 added a corrosion prevention clause, requiring that the metal components of louvered blinds undergo hot-dip galvanizing treatment with a coating thickness of ≥85μm.