Traditional counter-flow cooling towers have many advantages, but they also suffer from drawbacks such as small airflow cross-section, low flow rate, and high flow resistance, which affect cooling efficiency. Therefore, if the airflow cross-sectional area can be increased and heat and mass transfer improved, this type of counter-flow closed-circuit cooling tower would be a more competitive tower design.
This structure involves packing material in the upper part of the closed-circuit cooling tower and tube bundles in the lower part. Air inlets are located on two sides in the middle of the cooling tower. Air enters the cooling tower through these inlets and splits into two paths: one flows upward through the packing material and exits at the top of the cooling tower, while the other flows downward through the tube bundle and then upward through an exhaust duct located on the two sides without air inlets, exiting at the top of the cooling tower. Inside the cooling tower, spray water flows from top to bottom, while the fluid to be cooled within the tube bundle flows from bottom to top. Thus, the airflow in the tube bundle and the flow of the fluid being cooled within the tubes are counter-current, as are the airflow in the packing material and the spray water. This counter-current flow pattern, with air intake in the middle and bidirectional flow in both directions, can increase the air circulation area, reduce the possibility of air backflow, and increase the average temperature difference or enthalpy difference between the spray water and the fluid, and between the air and the spray water. The kinetic potential energy of heat exchange is maintained within a reasonable range, thereby improving the heat and mass transfer effect, reducing the tube bundle area, and reducing costs.